Описание

Function Insulation monitor
System type DC
Nominal voltage to 280 V
Reponse value type Einstellbar
Reponse value kOhm ... kOhm 5 - 200 Ohm
Earth fault indicator +
Enclosure design Schaltschrank
Width 35 mm
Type SL 5881
According to IEC/EN 61 557-8 For DC voltage systems up to 12 ... 280 V Wide voltage range of measuring input UN DC 12 ... 280 V (on request DC 24 ... 500 V with separate auxiliary supply, Measuring range 20 ... 500 k&Omega,) Adjustable tripping value RAL of 5 ... 200 k&Omega, Selective ground fault indication for L+ and L- allows fast fault finding Without auxiliary supply De-energized on trip 2 changeover contacts Automatic or manual reset, programmable With test and reset buttons Connection for external test and reset button possible galvanic separated AC or DC auxiliary supply available as option adjustable time delay as option 2 models available:IL 5881: 61 mm deep with terminals near to the bottom to be mounted in consumer units or industrial distribution systems according to DIN 43 880SL 5881: 98 mm deep with terminals near to the top to be mounted in cabinets with mounting plate and cable ducts 35 mm width''